Medical gas supply. Assessment of space-planning solutions of the institution, selection of premises for the location of technical equipment

Systems Design medical gases is carried out taking into account the space-planning solutions of the building and existing utilities, the choice of premises for placing equipment, and the method of laying external pipelines. Selection of the complex technical devices- sources of gases, compressors and vacuum stations, shut-off and control valves, life support consoles, instrumentation depends on the characteristics and needs of the healthcare facility.

Medical gas supply pipelines

Pipeline networks are used for transportation and continuous supply of medical gases and providing vacuum to areas of patient treatment and the use of equipment - ventilators, anesthesia-respiratory equipment, surgical instruments. Bandwidth systems and source capacity must meet the facility's flow requirements. Pipe materials are selected based on compatibility with the transported gas and are corrosion resistant.

External pipelines

External pipeline networks are used only for centralized oxygen supply and are laid in two ways. The first option is openly on supports/overpasses and building facades. The second option is underground in trenches, tunnels or sleeves made of steel/asbestos-cement pipes.

Internal pipelines

The pipeline route is selected based on the location of the building’s utilities and requirements fire safety. The control unit with discharge ramps is located in a separate room with windows, which is located on optimal distance from the points of entry of external networks and is equipped supply- exhaust ventilation, monitoring and alarm systems.

Internal pipelines for supplying medical gases:

  • They have high mechanical strength in each section, withstanding a pressure 1.2 times higher than the maximum for a given zone.
  • They are located separately from elevator shafts, electrical wiring or at a distance of at least 50 mm from it.
  • They are grounded in the immediate vicinity of the point of entry into the building.
  • Protected from physical influences and damage, contact with corrosive materials.
  • They are fixed on supports to prevent deflections, bending and accidental displacements.
  • They are laid in the ceiling space, under ceilings and behind panels of wall and partition structures.

Pipeline sections are joined together by soldering or welding. Threaded connections are used in places where fittings are inserted, equipment is installed, and instrumentation is installed.

Shut-off and medical valves

Isolation of individual sections of pipelines for the purpose of maintenance, extension to increase the length of the network or shutting off in emergency situations is carried out using main shut-off valves, which are located on each riser and branch. Terminal devices and additional equipment are located after the local shut-off valve.

These include:

  • Room valves for use as shut-off valves when supplying medical gases to equipment.
  • Flow meters for dosing medical oxygen, equipped with humidifiers.
  • Rotamers with humidifiers to regulate the flow and humidification of medical oxygen supplied to the patient.
  • Vacuum regulators for connection to the outlet and smooth regulation of flow and degree of vacuum.
  • Ejection suction pumps for connection to the main line compressed air and aspiration in the absence of a vacuum supply system.
  • Valve systems with separate types of locks for connection medical equipment and equipment for medical gas supply networks.

Control and shutdown units, monitoring and alarm equipment are responsible for shutting off the flow, visually monitoring the pressure of the working medium and warning about unfavorable/emergency situations. Gas manifolds work with any media and provide automatic switching between main and backup sources. The alarm signal is sent to the alarm unit and monitoring panel.

Life support or medical gas supply consoles

Life support consoles are the terminal elements of medical gas supply systems. They are located in work area personnel or in close proximity to patients to supply 10 or more gases - oxygen, nitrous oxide, compressed air, carbon dioxide and providing vacuum, allow duplicating sources. If necessary, combinations of gases are used, the ratio of which in the mixture is adapted to the specific task.

Main types of life support systems:

  • Ceiling modules for operating rooms. They have a rotating arm and a coverage area of ​​3400, and are divided into two types depending on the purpose of use and the supplied gases. Surgical systems are equipped with valves for nitrous oxide, compressed air at 5 and 7 bar, oxygen and vacuum. In anesthesia consoles, high-pressure air is replaced by the removal of anesthetic gases.
  • Wall-mounted resuscitation modules for patients. Placed in intensive care units, intensive care units, and postoperative recovery rooms. They are equipped with valve systems for supplying oxygen, nitrous oxide, compressed air and providing vacuum and other gases, the quantity and type of which are determined at the design stage of the medical gas supply system.
  • Wall-mounted ward modules for patients. Used in cardiology, pulmonology, pediatric and other departments. They are equipped with valves for medical gases, which are specified by the customer during design.

After the installation of the medical gas supply system is completed, testing and commissioning are carried out.

Before commissioning a centralized medical gas supply, pipelines are checked for mechanical integrity and absence of leaks, flow rate at nominal pressure and performance, and dispersed contamination. Systems with oxygen generators and concentrators, dosing devices and compressors - on the quality of air used for breathing and the operation of surgical instruments. Local shut-off valves are tested for complete closure and leakage, terminal equipment, monitoring and alarm systems are tested for correct operation and performance of their functions.

The specificity of the system for a particular gas is confirmed by installing and fixing a nipple of a certain type. This eliminates the possibility of errors in connecting to the network and supplying medical gas or vacuum.

Medical gas supply systems are put into operation after testing to confirm their compliance with requirements and certification. The health facility is provided with inspection reports, instructions for the operation of each component, management and maintenance.

Therapeutic gas supply includes the following systems:

  • supply of medical oxygen (hereinafter referred to as oxygen);
  • supply of nitrous oxide;
  • supply of compressed air with a pressure of 4 Bar;
  • supply of compressed air with a pressure of 7 bar;
  • carbon dioxide supply;
  • provision of vacuum;
  • nitrogen supply;
  • provision of argon.

Typical equipment in hospitals using nitrous oxide should include anesthetic gas removal systems.

Each therapeutic gas supply system consists of a source of appropriate gas, pipelines transporting gas, gas consumption points and a gas supply control system.

A necessary condition for the life support systems of a modern hospital is the continuous operation of the equipment, for which all sources included in the systems medicinal gases, are duplicated for the possibility of replacing elements without stopping the supply of therapeutic gases to the consumption lines.

Typical equipment of a hospital medical gas supply system should be designed in such a way as to ensure its autonomous operation in different fire compartments in which consumers of therapeutic gases are located.

The centralized oxygen supply system consists of the following elements:

  • source of oxygen supply;
  • external network of oxygen pipelines;
  • internal oxygen supply system.

Medical organizations use medical gaseous oxygen in accordance with GOST 5583-78 and liquid oxygen in accordance with GOST 6331-78.

Depending on the amount of oxygen consumed and local conditions (presence of gaseous or liquid oxygen), the source of oxygen supply can be:

  • oxygen-gasification station;
  • 40-liter oxygen cylinders with a gas pressure of 150 atm.;
  • oxygen generator (concentrator).

With a quantity of 40-liter oxygen cylinders more than 10 pieces should be placed in a central oxygen point - a separate heated building.

The oxygen ramp is used in medical organizations as the main source when the facility’s oxygen demand is small, and also as a backup when there is a main source of oxygen - an oxygen-gasification station or a central oxygen point.

The total capacity of the cylinders must provide a supply of oxygen for the operation of the treatment and prevention organization for at least 3 days.

The oxygen generator can be placed both inside the building (in a separate room with window openings, located taking into account the places of maximum consumption, on the 1st and upper floors) and outside the building in a special container equipped with lighting, heating and air conditioning systems. The oxygen generator installation includes: air compressor, compressed air preparation unit for the oxygen generator (filters, compressed air dryer), oxygen generator, air and oxygen receivers, control unit.

Installations in containers can be equipped with stations for filling produced oxygen into cylinders, which can be used as backup sources of oxygen.

External networks of oxygen pipelines are laid underground in trenches with mandatory backfilling of the trenches with soil.

External oxygen pipeline networks are made of seamless cold- and heat-deformed pipes made of corrosion-resistant steel GOST 9941-81 with a wall thickness of at least 3 mm.

It is allowed to lay oxygen pipelines above ground along the facades of buildings from copper pipes grade T in accordance with GOST 617-72 or from seamless cold- and heat-deformed pipes made of corrosion-resistant steel in accordance with GOST 8941.

On underground oxygen pipelines when they cross highways, driveways and other engineering structures provide cases made of asbestos-cement pipes for non-pressure pipelines according to GOST 1839-80.

Typical equipment of hospitals with external network oxygen pipelines are carried out in accordance with the requirements of VSN 49-83, VSN 10-83 and SNiP 3.05.05-84.

Oxygen enters the internal system from external networks through an oxygen manifold, combined with pipelines of other therapeutic gases into a control (distribution) unit, where shut-off valves and instrumentation are installed on the oxygen pipelines. On oxygen pipelines, only fittings specifically designed for oxygen should be installed (brass, bronze, stainless steel, lined). The use of steel and cast iron reinforcement is not allowed.

Oxygen supply in standard hospital equipment is provided in the following rooms: operating rooms; anesthesia; resuscitation rooms; pressure chamber premises; maternity wards; recovery rooms; intensive care wards (including children's and newborns); dressings; procedural departments; blood collection rooms; procedural endoscopy and angiography; wards for 1 and 2 beds of all departments, except psychiatric ones; wards for newborns; wards for premature babies.

Medical organizations use medical nitrous oxide (liquefied gas). State Pharmacopoeia of the Russian Federation, 12th edition 2007, part I.

The centralized supply system for nitrous oxide consists of a source of liquefied gas and an internal network of pipelines from the source to the points of consumption. Typical hospital equipment involves supplying nitrous oxide to the following rooms: operating rooms; anesthesia; procedural angiography, endoscopy, bronchoscopy; maternity wards; prenatal wards; burn department wards; intensive care wards (according to design specifications), incl. for children and newborns.

The supply of nitrous oxide is carried out from two groups of ramps for 10-liter cylinders with nitrous oxide (one group is working, the other is reserve). When the cylinders of the working group are emptied, the nitrous oxide unit automatically switches to the operation of the reserve group. Ramps for cylinders with nitrous oxide are located in the same medicinal gas control room where the medicinal gas control and distribution units are located, i.e. in a room with window openings on any floor of the building, except basements (preferably closer to the place highest consumption).

The vacuum supply system consists of a vacuum source - a vacuum station and a pipeline network. Vacuum stations are located in the basement or ground floor under secondary rooms (lobby, wardrobe, linen storage, etc.).

The supply of vacuum network pipelines is provided in: operating rooms; anesthesia; resuscitation rooms; maternity wards; recovery rooms; intensive care wards; dressings; procedural angiography, endoscopy, bronchoscopy; wards for 1 and 2 beds of all departments (as per design specifications), except for psychiatric ones; wards of cardiology and burn departments; wards for newborns; wards for premature babies.

To provide consumers with compressed air, compressed air stations are provided as sources. When placing and installing compressed air stations, you should be guided by the “Rules for the design and safe operation of stationary compressor units, air and gas pipelines.” In medical institutions, compressed air stations can be located in the basement or ground floor under rooms without permanent occupancy (lobby, wardrobe, linen storage, etc.). The supply of compressed air pipelines is provided for operating rooms, anesthesia rooms, intensive care rooms, labor rooms, and dressing rooms; intensive care wards, post-operative wards, wards for patients with skin burns, wards for newborns and premature babies, endoscopy procedures, as well as in inhalation rooms, bathrooms and laboratories.

The use of carbon dioxide is envisaged in operating rooms where laparoscopic and cryogenic techniques are used (cryodestruction devices), as well as in bathrooms and embryological rooms (and other rooms with CO2 incubators). The supply of carbon dioxide is carried out from a two-arm ramp (one arm of the ramp is working, the other is reserve) for 40-liter cylinders with carbon dioxide. Ramps for carbon dioxide cylinders are located in the same therapeutic gas control room where the control and distribution units for therapeutic gases are located and nitrous oxide ramps are located, i.e. in a room with window openings on any floor of the building, except basements (preferably closer to the place of greatest consumption).

Pipelines for therapeutic gases are made of copper pipes grade “T” in accordance with GOST 617-72 using fittings (tees, bends, etc.).

To supply compressed air to inhalers, bathrooms and laboratories, it is possible to use seamless cold- and heat-deformed pipes made of corrosion-resistant steel in accordance with GOST 9941, in laboratories - from galvanized steel water-gas pipes in accordance with GOST 3332.

Copper pipes for laying internal networks medicinal gases must be seamless and fat-free. Copper pipes must be connected to each other by soldering or using pipe fittings that meet the requirements of current standards and have a permit issued in accordance with the established procedure. Where they pass through ceilings, walls and partitions, pipes are placed in protective cases (sleeves) made of water and gas pipes according to GOST 3262-75.

In places where medical gases are consumed, either separate gas valves are installed on the wall, at a height of 1400 mm from the floor, or wall or ceiling panels(consoles) with gas valves installed in them.

Therapeutic gas systems must include automatic regulators that provide:

  • - automatic switching from the working group of cylinders to the reserve one in case of emptying of the working group for cylinder stations of nitrous oxide, carbon dioxide, oxygen;
  • - block automatic alarm in case of deviation from the specified pressure of therapeutic gases;
  • - automatic switching on of backup compressors and vacuum pumps;
  • - alternate activation of compressors and vacuum pumps.

Medical institutions must provide a centralized medical gas supply in accordance with regulatory documents:

  • GOST 12.2.052-81, OST 290.004.
  • GOST 9941-81 Seamless cold- and heat-deformed pipes made of corrosion-resistant steel. technical conditions
  • GOST 617-2006 Copper pipes. Specifications
  • VSN 49-83. Departmental building standards. Instructions for the design of interplant pipelines for gaseous oxygen, nitrogen, argon
  • VSN 10-83 Ministry of Chemical Industry. Instructions for the design of gaseous oxygen pipelines
  • SNiP 3.05.05-84. Technological equipment and process pipelines
  • SNiP 42-01-2002 Gas distribution systems
  • STO 002 099 64.01-2006 Rules for the design of production facilities for air separation products

For several years, WestMedGroup has been designing and commissioning medical and technical gas supply systems, as well as medical valve systems based on equipment of its own production and the French company MIL"S. Our company’s specialists will help you select equipment for gas supply systems depending on the needs of the institution.

No medical institution can do without the following medical gases - medical oxygen O2 (gaseous GOST 5583-78 and liquid GOST 6331-78), carbon dioxide CO2, nitrous oxide N2O. Also, medical institutions often use compressed air and vacuum cylinders. In the course of their work, hospitals also use mixtures of gases. Any clinical case may require its own specific composition of the mixture of medical gases. It is quite common to use mixtures of oxygen and carbon dioxide, oxygen and helium, oxygen and xenon, and other mixtures. The systems for supplying these medical gases from the source to the patient constitute the medical gas supply.

Today we offer a wide range of gas supply services medical institutions. This includes:
- installation of oxygen generators;
- installation of compressed air stations;
- installation of vacuum stations;
- laying of pipeline systems;
- arrangement of communications for the supply of medical gases in medical institutions;
- installation of final equipment for connecting medical gas supply systems to the patient;
- commissioning of installed equipment;
- other related works and services.

The therapeutic gas system designs we offer comply with international standards ISO 7396-1:2007, ISO 10083:2006, ISO 10524-1:2006. They guarantee an uninterrupted supply of the necessary medical gases directly to the patient thanks to the use of following principles:
- duplication of all sources of medical gas supply in case of failure;
- in order to achieve pressure stability at all points of the system, including remote ones), pipes of different diameters are used, as well as pipe routing in the form of a branch;
- it is necessary to eliminate as much as possible sharp installation bends of pipes, as they can lead to unnecessary differences in flow and pressure;
- provision of an automatic control system in case of medical gas leaks from the system or malfunction of the supply system itself;
- the system must be built modularly so that it is always possible to turn off one of the modules without disrupting the supply of other modules, that is, the modules should not depend on each other;
- use sockets for instant connection
- points of consumption must be equipped with instant connection sockets for medical gases DIN standard.

Main components of the system:
1. Centralized sources of medical gases (oxygen, compressed air and vacuum stations).
2. Control equipment.
3. Medical gas pipelines.
4. Systems for creating a workplace (resuscitation and operating modules, ward modules).

Necessary stages of work on medical gas supply.
1. System design.
2. Supply and installation of specialized equipment for the medical gas supply system.
3. Activities for commissioning and debugging of equipment.
4. Warranty and post-warranty maintenance of the installed system.

Project for centralized supply of the facility: “Surgical building, 5th floor. Major renovation operating block" of the Kaluga Regional Clinical Hospital (hereinafter referred to as the "Block") with oxygen, nitrous oxide, compressed air at a pressure of 4.5 and 8 bar, carbon dioxide, as well as providing consumers with vacuum is made in accordance with the architectural, construction and technological parts of the project and the Customer’s assignment in accordance with modern requirements for equipping hospitals with medical gases.

1. Centralized oxygen supply.

Oxygen at a pressure of 4.5 bar for the Unit is supplied to operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic), small operating rooms and recovery rooms.
Total and point oxygen consumption were calculated according to the “Manual
on the design of medical institutions" to SNiP 2-08-02-89 and are given
in table 1:

Medical gaseous oxygen GOST 5583-78 is used in medical institutions.
Oxygen at a pressure of 4.5 bar is supplied to the Block’s consumers from the existing oxygen-gasification station based on two VRV 3000 gasifiers.

The total oxygen consumption by the Unit's consumers is 40,050 l/day. (Oxygen output from one cylinder with a capacity of 40 liters is 6000 liters. Thus, the Block’s theoretical need for oxygen is ~ 6.7 cylinders per day).
The connection of the Block's consumers to the oxygen supply system is carried out in the corridor of the 5th floor to the existing riser. Taking into account the presence of an existing input unit into the housing, the design does not provide for a secondary reduction unit.
From the connection point, oxygen is supplied to consumers through a horizontal pipeline in the suspended ceiling through control disconnect boxes.
In operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic) and small operating rooms, ceiling consoles for the anesthesiologist and surgeon and additionally accommodates wall consoles that duplicate the ceiling ones in terms of the set of medical gases. .
In the awakening wards, individual ceiling systems type "B.O.R.I.S".

The terminal devices (valve systems) included in the consoles for oxygen must have an individual input geometry in accordance with the DIN EN standard, which will eliminate errors when connecting the equipment.
The valves must be provided with quick-release connections that allow connection to be made within a few seconds.
The designed oxygen pipelines should be installed from copper pipes in accordance with GOST 617-2006. Install a shut-off valve at the outlet from the riser for technological shutdowns of equipment and testing of pipelines for strength and density.
The mounted ceiling and wall mounting consoles must be supplied with electrical cables, designed for the connected load specified in the task (determined by the TX section based on the characteristics of the connected equipment).
All oxygen supply system equipment must operate around the clock, have appropriate color markings and explanatory notes in Russian.
Before installation, pipes must be degreased in accordance with STP 2082-594-2004 "Cryogenic equipment. Degreasing methods."
The entire volume of medical gases intended for installation of the system must be degreased.
It is recommended to degrease oxygen pipelines using the following aqueous cleaning solutions (Table 2).
Used to prepare solutions drinking water according to GOST 2874-82. The use of water from the recycling water supply system is unacceptable.
The outer surface of the ends of pipes for a length of 0.5 m is degreased by wiping with napkins soaked in a cleaning solution, followed by drying in the open air.
After installation, the pipelines must be tested pneumatically for strength and tightness. Pipelines must be tested for strength and tightness in accordance with SNiP 3.05.05-84 and PB 03-585-03.

The test pressure value should be taken in accordance with table. 3
During pneumatic testing, the pressure in the pipeline should be increased gradually with inspection at the following stages: upon reaching 30 and 60% of the test pressure - for pipelines operated at an operating pressure of 0.2 MPa and above. During the inspection, the pressure rise stops.
Leak locations are determined by the sound of air leaking in, as well as bubbles when covering welds and flange joints with soap emulsion and other methods. Defects are eliminated by reducing overpressure to zero and turning off the compressor.
The final inspection is carried out at operating pressure and is usually combined with a leak test.
If during testing of equipment and pipelines defects made during production are identified installation work, the test must be repeated after the defects have been eliminated.
Before the start of pneumatic tests, the installation organization must develop instructions for the safe conduct of test work in specific conditions, which all test participants must be familiar with.
The final stage of individual testing of equipment and pipelines should be the signing of their acceptance certificate after individual testing for comprehensive testing.
The compressor and pressure gauges used when conducting pneumatic testing of pipelines should be located outside the security zone.
Special posts are installed to monitor the security zone. The number of posts is determined based on the conditions so that the security of the zone is reliably ensured.
The pipelines, after all tests have been carried out, are purged with oil-free air or nitrogen, and before commissioning - with oxygen and released outside the building.
Pipelines must be purged under pressure equal to the working pressure. The duration of purging should be at least 10 minutes. During purging, devices, control and safety valves are removed and plugs are installed.
During pipeline purging, fittings installed on drain lines and dead-end sections must be completely open, and after purging is completed, they must be thoroughly inspected and cleaned.
To protect equipment and pipelines from static electricity the latter must be reliably grounded in accordance with the “Rules for protection against static electricity in the chemical, petrochemical and oil refining industries”.
Grounding devices for protection against static electricity should generally be combined with grounding devices for electrical equipment. Such grounding devices must be made in accordance with the requirements of Chapters I-7 and VII-3 of the Electrical Installation Rules (PUE).
The resistance of the grounding device, intended solely for protection against static electricity, is allowed up to 100 ohms.
Pipelines must be continuous throughout their entire length. electrical circuit, which within the facility must be connected to the ground loop at least at two points.
Workers who have undergone training and passed tests are allowed to make permanent connections from non-ferrous metals and alloys. Welding of pipelines made of non-ferrous metals is allowed to be carried out at an ambient temperature of at least 5 °C. The surface of the ends of pipes and pipeline parts to be connected must be processed and cleaned in accordance with the requirements of departmental regulations and industry standards before welding.
The bending radii of pipes should be R = 3 Dn (Dn - outer diameter). Various (flange and threaded) connections may only be used when connecting pipelines to fittings, equipment and in places where instrumentation is installed.
Where they pass through ceilings, walls and partitions, pipes are placed in protective cases (sleeves) made from water and gas pipes. The space between the pipe and the case is sealed with sealant.
The edges of the case (sleeve) should be placed at the same level with the surface of the walls, partitions and ceilings.
Lay pipelines:

- in operating rooms, recovery rooms ("Clean Rooms" zone) - at a height of 100 mm below the level of overlap with a soft pipe without solder seams.
Install oxygen pipelines in a space free from other communications.
The laying of oxygen pipelines before installation is coordinated with electricians, and the installation of pipelines is carried out only after the installation of ventilation, sanitary and electrical equipment is completed.

2. Centralized supply of nitrous oxide.
Nitrous oxide at a pressure of 4.5 bar for the Block is supplied to operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic) and small operating rooms.
Estimated nitrous oxide costs are shown in Table 4:
In medical institutions, medical nitrous oxide (liquefied gas) VFS 42U-127/37-1385-99 is used.
Nitrous oxide at a pressure of 4.5 bar is supplied to the consumers of the Unit from the discharge balloon ramp, located in the nitrous oxide unit (No. 5.15, 5th floor). Ramp capacity: 12 cylinders (2 groups of 6 cylinders). There is a block automatic switching ramp shoulders. According to the previously existing Manual for the design of healthcare institutions (to SNiP 2.08.02-89*) part 1, the room in which nitrous oxide cylinders are located can be located in a room with window openings on any floor of the building, except the basement (preferably closer to the place of greatest consumption. The room must be equipped with exhaust ventilation. Room category in accordance with SP 12.13130.2009 - D.
The total consumption of nitrous oxide is 11,340 l/day. (The yield of nitrous oxide from one cylinder with a capacity of 10 liters is 3000 liters. Thus, the Center’s need for nitrous oxide is ~ 3.8 cylinders per day).
In rooms provided with nitrous oxide, waste narcotic gases are removed using the ejection method using compressed air. Exhaust gas is discharged outside the building locally from each room through a designed pipeline system with release into the atmosphere.
From the discharge ramp, nitrous oxide is supplied to consumers through a horizontal pipeline located in the suspended ceiling through control disconnect boxes. Nitrous oxide flow valves are installed in the same consoles to which oxygen is supplied (see section 1).
The terminal devices (valve systems) included in the consoles for nitrous oxide must have an individual input geometry in accordance with the European standard DIN EN, which will eliminate errors when connecting the equipment.
All equipment of the nitrous oxide supply system must operate around the clock, have appropriate color coding and explanatory notes in Russian.
The designed nitrous oxide pipelines should be installed from copper pipes in accordance with GOST 617-2006.
After installation, nitrous oxide pipelines must be tested pneumatically for strength and tightness.

Pneumatic testing should be carried out with medical air and only during daylight hours.
The test pressure value should be taken in accordance with table. 5


The nitrous oxide pipeline, after all tests have been carried out, is purged with oil-free air or nitrogen, and before commissioning - with nitrous oxide and released outside the building.
Protection of equipment and nitrous oxide pipelines from static electricity is carried out similarly to the protection of oxygen pipelines (see Section 1).

Lay the nitrous oxide pipeline:
- in the corridors: behind suspended ceiling, and in places of lowering - openly (in the electrical box);
- in operating rooms ("Clean Rooms" zone) - at a height of 100 mm below the level of overlap with a soft pipe without solder joints.
Installation of nitrous oxide pipelines should be carried out in a space free from other communications.
The laying of nitrous oxide pipelines before installation is coordinated with electricians, and the installation of pipelines is carried out only after the installation of ventilation, sanitary and electrical equipment is completed.

3.Centralized compressed air supply.
Compressed air with a pressure of 4.5 bar for the Unit is supplied to operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic), small operating rooms and recovery rooms.
Compressed air with a pressure of 8 bar for the Unit is supplied to the operating rooms (trauma and orthopedic) and the dismantling and washing rooms of the NDA in accordance with the instructions of the technical specifications section.
Compressed air quality must meet the requirements of GOST 17433-80 (for the presence of solid particles and foreign impurities - correspond to pollution class “0”, dew point taking into account the location of the compressor equipment + 30C).
Compressed air with a pressure of 4.5 bar in the project performs two functions:
- serves for the operation of anesthesia-respiratory equipment;
- serves to remove narcotic gases.
Compressed air with a pressure of 8 bar in the project performs two functions:
- serves to ensure the operation of pneumatic surgical instruments;
- used when servicing NDA.
Due to the lack of Russian standards for calculations centralized system compressed air, this calculation was carried out according to European standards.
The calculated compressed air costs are given in Table 6:
Compressed air with a pressure of 4.5 bar and 8 bar is supplied to the consumers of the Unit from a designed compressor station based on 4 compressors located in the basement (rooms 4.5) in accordance with the requirements of the Rules for the Design and Safe Operation of Vessels Operating under Pressure PB 03-576-03 and Rules for the design and safe operation of stationary compressor units, air and gas pipelines.
Category of premises in accordance with SP 12.13130.2009 - B4.
It is proposed to use BOGE (Germany) SC 8 compressors.
Each compressor unit provides the calculated consumption of the Unit’s medical premises in compressed air at pressures of 4.5 bar and 8 bar. Overall dimensions of the compressor LxWxH 830x1120x1570 mm. The capacity of each compressor is 0.734 m3/min at a maximum pressure of 10 bar, power consumption is 5.5 kW (~3x400 V). Receivers 500 l galvanized. Basic control and monitoring system, 24 V control voltage. For air drying, refrigerated air dryers DS 18 are used. Dew point +3°. The air treatment system ensures air purification from microparticles down to 0.01 microns in size, and from oil up to 0.003 mg/m3. BOGE filters (Germany) are accepted for installation
The total compressed air consumption is:
- pressure 4.5 bar - 490 l/min;
- pressure 8 bar - 555 l/min.
From the compressor room, compressed and purified air is supplied to consumers through designed risers and branches through control disconnect boxes.
Compressed air flow valves in rooms are installed in the same consoles to which oxygen is supplied (see Section 1).
Quantity terminal devices in each room is determined by the technical specifications.
In rooms provided with compressed air at a pressure of 8 bar, waste air is removed from pneumatic tools. Exhaust air is discharged outside the building locally from each room through a designed piping system with release into the atmosphere.
In the NDA washing rooms, shut-off valves are used as terminal devices.
The terminal devices (valve systems) included in the consoles for compressed air of each pressure have an individual input geometry in accordance with the European standard DIN EN, which will eliminate errors when connecting the equipment.
All compressed air supply system equipment must operate around the clock, have appropriate color coding and explanatory notes in Russian.
The designed compressed air pipelines should be installed from copper pipes in accordance with GOST 617-2006. Install on the branches from the riser shut-off valves for technological shutdowns of equipment and testing of pipelines for strength and density.
After installation, compressed air pipelines must be tested pneumatically for strength and tightness.
Pipelines must be tested for strength and tightness in accordance with SNiP 3.05.05-84 and PB 03-585-03. Pneumatic testing should be carried out with medical air and only during daylight hours. The test pressure value should be taken in accordance with table. 7
The testing procedure is similar to testing oxygen pipelines (see Section 1).
Protection of equipment and compressed air pipelines from static electricity is carried out similarly to the protection of oxygen pipelines (see Section 1).
The qualification requirements for solder welders are similar to the requirements for oxygen pipeline welders (see Section 1).
Lay the compressed air pipeline:
- in corridors: behind a suspended ceiling, and in places of lowering - openly (in an electrical box);
- in operating rooms, recovery rooms ("Clean Rooms" zone) - at a height of 100 mm below the ceiling level.
Install compressed air pipelines in a space free from other communications.
The laying of compressed air pipelines before installation is coordinated with electricians, and the installation of pipelines is carried out only after the installation of ventilation, sanitary and electrical equipment is completed.

4. Centralized supply of vacuum.

Vacuum in the Block is provided in operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic), small operating rooms and recovery rooms.
The calculation of the vacuum system was carried out according to Russian standards.
The Block's consumers are provided with vacuum from a designed vacuum station based on a duplex central vacuum unit on a horizontal air collector; LxWxH no more than 2300x1000x1900; Q not less than 2x40 m³/hour; W no more than 2x3 kW, manufactured by Medgas-Technik (Germany), located in the basement (room 47). Supply voltage ~ 380, three-phase, 50 Hz. The air pumped out from the vacuum pipeline, before entering the air collector, passes through a filter system and only then is discharged outside the building at a height of at least 3.5 m from the ground level.
Category of premises in accordance with SP 12.13130.2009 - D.
From the premises of the vacuum station, vacuum is supplied to consumers through the designed riser and branches through control disconnect boxes.
Vacuum flow valves in rooms are installed in the same consoles to which oxygen is supplied (see Section 1).
The number of terminal devices in each reconstructed room is determined by the technical specifications.
The terminal devices (valve systems) included in the consoles for vacuum have an individual input geometry in accordance with the European standard DIN EN, which will eliminate errors when connecting the equipment.
All equipment of the vacuum supply system must operate around the clock, have appropriate color markings and explanatory notes in Russian.
Vacuum pipelines should be installed from copper pipes in accordance with GOST 617-2006. Install shut-off valves on a branch from the riser for technological shutdowns of equipment and testing of pipelines for strength and density.
After installation, vacuum pipelines must be tested pneumatically for strength and tightness.
Pipelines must be tested for strength and tightness in accordance with SNiP 3.05.05-84 and PB 03-585-03.
Pneumatic testing should be carried out with medical air and only during daylight hours.
The test pressure value should be taken in accordance with table. 8
The testing procedure is similar to testing oxygen pipelines (see Section 1).
After all tests have been completed, vacuum pipelines are purged with oil-free air or nitrogen and released outside the building.
Installed vacuum pipelines must be subjected, in addition to pneumatic testing, to a vacuum test.
After creating a vacuum of 400 mmHg. Art. the vacuum line is disconnected from vacuum installation, after which the vacuum drop should not exceed 10% within two hours.
Protection of equipment and vacuum pipelines from static electricity is carried out similarly to the protection of oxygen pipelines (see Section 1).
The qualification requirements for solder welders are similar to the requirements for oxygen pipeline welders (see Section 1).
Lay the vacuum pipeline in the reconstructed area:
- in corridors: behind a suspended ceiling, and in places of lowering - openly (in an electrical box);
- in operating rooms and recovery rooms ("Clean Rooms" zone) - at a height of 100 mm below the ceiling level.
Installation of vacuum pipelines should be carried out in a space free from other communications.
The laying of vacuum pipelines before installation is coordinated with electricians, and the installation of pipelines is carried out only after the installation of ventilation, sanitary and electrical equipment is completed.
5.Providing carbon dioxide
Carbon dioxide at a pressure of 4.5 bar for the Block is supplied to operating rooms (general, urological, traumatological, orthopedic, neurosurgical, thoracic, septic) and a small operating room.
Since there are no data on carbon dioxide consumption in Russian standards, we will take the carbon dioxide consumption per point equal to 5 l/min, and the duration and simultaneity coefficient by analogy with oxygen.
Carbon dioxide with a pressure of 4.5 bar is supplied to the consumers of the Unit from a discharge cylinder ramp located in the nitrous oxide unit room (No. 5.15, 5th floor). Ramp power 4 cylinders (2 groups of 2 cylinders). There is a block for automatic switching of ramp arms. The room must be equipped with exhaust ventilation. Category of premises in accordance with SP 12.13130.2009 - D.
The total consumption of carbon dioxide is 9,450 l/day. (The output of carbon dioxide from one cylinder with a capacity of 40 liters is 12500 liters. Thus, the Block’s need for carbon dioxide is ~ 0.8 cylinders per day).
From the discharge ramp, carbon dioxide is supplied to consumers through a horizontal pipeline located in the suspended ceiling through control disconnect boxes. Carbon dioxide flow valves are installed in ceiling-mounted surgical/endoscopic and backup consoles.
The terminal devices (valve systems) included in the consoles for carbon dioxide must have an individual input geometry in accordance with the European standard DIN EN, which will eliminate errors when connecting the equipment.
All equipment of the carbon dioxide supply system must operate around the clock, have appropriate color coding and explanatory notes in Russian.
The designed carbon dioxide pipelines should be installed from copper pipes in accordance with GOST 617-2006.
After installation, carbon dioxide pipelines must be tested pneumatically for strength and tightness.
Pipelines must be tested for strength and tightness in accordance with SNiP 3.05.05-84 and PB 03-585-03.
Pneumatic testing should be carried out with medical air and only during daylight hours.
The test pressure value should be taken in accordance with table. 10
The testing procedure is similar to testing oxygen pipelines (see Section 1).
The carbon dioxide pipeline, after all tests have been carried out, is purged with oil-free air or nitrogen, and before commissioning - with carbon dioxide released outside the building.
Protection of equipment and carbon dioxide pipelines from static electricity is carried out similarly to the protection of oxygen pipelines (see Section 1).
The qualification requirements for solder welders are similar to the requirements for oxygen pipeline welders (see Section 1).
Lay the carbon dioxide pipeline:
- in corridors: behind a suspended ceiling, and in places of lowering - openly (in an electrical box);
- in operating rooms ("Clean Rooms" zone) - at a height of 100 mm below the ceiling level.
Installation of carbon dioxide pipelines should be carried out in a space free from other communications.
The laying of carbon dioxide pipelines before installation is coordinated with electricians, and the installation of pipelines is carried out only after the installation of ventilation, sanitary and electrical equipment is completed.
Transportation of cylinders along the street is carried out using a transportation trolley gas cylinders. The cylinder is lifted to the floor in an elevator. When transporting, avoid dropping or knocking the cylinder. It is forbidden to carry the cylinder while holding it by the valve.
DWG format.
Design engineer Trostin

Special attention is always paid to the equipment of medical institutions. Doctors use equipment whose operation has been thought out to the smallest detail: each “gear” rotates at its own frequency and the slightest failure can lead to dangerous consequences.

Medical gas supply is an important area that requires a special approach. Gas supply systems are placed taking into account the profile of the medical institution: everything is taken into account, from the volume of gas consumption to the specifics of the personnel’s activities. However, all medical gas supply systems have the same operating principle.

Purpose of medical gas supply systems

Medical gas supply systems are needed for life support for patients and for organizing the workspace of staff. They are used in intensive care units and operating rooms, wards, and therefore are an important link in ensuring the functioning of any hospital.



The design of medical gas supply occurs in such a way that patients and hospital employees do not have direct contact with the installation site of the system. Most often, the area for the location of gas tanks and their control system are basements, specially equipped places.

Medical gas supply is installed taking into account the required safety requirements. Modules of control and shutdown valves are installed on the main gas pipeline line to prevent an emergency. Using this mechanism, you can quickly turn off the gas supply in case of danger.

Design and installation of medical gas supply

New technologies make it possible to monitor the operation of medical gas supply systems using electronic monitors. They help prevent emergency situations or promptly respond to their occurrence.

The professionalism of the workers who install these systems is also important. In this case, you need to trust only specialists in this field with extensive experience.

Preliminary design of medical gas supply must take into account the operating features of the equipment, customer requirements and the conditions and parameters of the premises where installation will be carried out.

Our company guarantees:

  • Use of European materials from leading manufacturers.
  • Design and installation of medical gas supply systems by experienced specialists.
  • Possibility of full service and post-warranty service.

Don't take risks - entrust the installation of medical gas supply systems to professionals! The Oxygen Service company offers the supply and installation of equipment for healthcare institutions from leading manufacturers. You can order a comprehensive service from us - delivery, installation and subsequent maintenance. All products are certified, and design and installation work is carried out taking into account modern standards and the wishes of the client.